Integrity reinforcement
Based on AS3600 2018(+A2) Clause 9.2

Table of Contents

Background

Clause 9.2.2 Minimum structural integrity reinforcement

The summation of the area of bottom reinforcement connecting the slab, drop panel, or slab band to the column or column capital on all faces of the periphery of a column or column capital shall be not less than,

\[ A_{s.min} = \frac{2N^*}{\Phi f_{sy}} \]

in which N* is the column reaction from the floor slab at the ultimate limit state. Integrity reinforcement shall not be required if there are beams containing shear reinforcement and with at least two bottom bars continuous through the joint in all spans framing into the column.

Strength parameters

Slab reaction, N* kN

Rebar strength, fsy MPa

Strength reduction factor, Φ

Bar length parameters

Column Dx mm

Column Dy mm

Concrete strength, f'c MPa

Cover mm

Spacing, a mm

Integrity reo

Custom bars

Bars N

Bar area, As mm2

Integrity capacity kN

Basic development length, Lsy.tb mm

Length X-X mm

Length Y-Y mm